Carbon monoxide (CO) is a colorless, odorless gas produced by incomplete combustion. In parking garages it comes mostly from cold starts and idling gasoline engines, and it is the main pollutant that enclosed-garage ventilation is designed to control.
Open garages ventilate naturally. Enclosed and below-grade garages need a mechanical ventilation system, sized under the International Mechanical Code at 0.75 cfm per square foot of floor area unless an approved gas detection system controls the fans.
Exposure benchmarks
- EPA outdoor standard: 9 ppm over 8 hours.
- NIOSH recommended limit: 35 ppm over 8 hours; 200 ppm ceiling.
- OSHA permissible limit: 50 ppm over 8 hours.
- Immediately dangerous to life or health: 1,200 ppm.
Sensing and savings
- Gas detection. CO sensors, plus nitrogen dioxide sensors where diesel vehicles park, let fans run at a low base rate and ramp up when readings rise. See demand-controlled ventilation.
- Drives. Variable frequency drives let fans slow down, and fan power falls roughly with the cube of speed.
- Calibration. Sensors drift and expire; a dead sensor can leave fans idling or running flat out.
- Electric vehicles. EVs emit no CO, but codes still require ventilation sized for mixed fleets, and booths, cashiers and attendants still breathe the air.
The Parkonomics view
Garage ventilation is a health system that happens to be one of the biggest energy loads in the building. Sensors and drives let it be both safe and cheap, as long as someone calibrates the sensors.